Lesson 2 of 4 35 min

Motor Control and Contactors

Direct-on-line starting, contactor control circuits, overload protection and the alternatives for larger or more demanding drives.

In this lesson
  • Explain how a contactor and a control circuit start a motor
  • Calculate the input current of a motor from output power, efficiency and power factor
  • Describe the purpose of an overload relay and of a soft starter or variable-frequency drive

A motor control circuit has two sides: the power circuit, which carries the motor current through the contactor and protection, and the control circuit, which energises the contactor coil. The control circuit usually operates at a lower voltage and includes start and stop buttons, auxiliary contacts and protective interlocks.

Direct-on-line starting

In a direct-on-line starter the contactor applies full line voltage to the motor. Starting current is substantially higher than running current, so the supply, protection and mechanical system must tolerate the start. For larger motors, reduced-voltage starting or a variable-frequency drive limits the starting current and the mechanical shock.

P_input = P_output ÷ η
Mechanical output power divided by efficiency gives electrical input power.
I_line = P_input ÷ (√3 × V_line × cos φ)
Line current of a balanced three-phase motor.
Worked example

Motor line current

Problem. A 7.5 kW three-phase motor has an efficiency of 0.90 and a power factor of 0.85 on a 400 V supply. Estimate its line current.

Solution. P_input = 7500 ÷ 0.90 = 8333 W. I = 8333 ÷ (√3 × 400 × 0.85) = 8333 ÷ 588.9 = 14.15 A, approximately 14.2 A.

Overload protection

An overload relay protects the motor against sustained overcurrent, not against a short circuit — the short-circuit protection is provided by a fuse or circuit breaker. The relay’s setting must match the motor’s rated current and the manufacturer’s instructions, and it must be coordinated with the motor’s starting profile.

  • The contactor switches the motor circuit under the command of the control circuit.
  • The control circuit is typically at a lower voltage and includes interlocks.
  • An overload relay protects against sustained overcurrent, not short circuits.
  • A variable-frequency drive controls speed and limits starting current.
  • Local standards govern control-circuit voltages, colour codes and isolation requirements.
The motor nameplate and the manufacturer’s data are the authority for rated current, connection and protection settings. A current calculated from a generic efficiency and power factor is only an estimate.
Key points.
  • A contactor switches the power circuit; the control circuit drives its coil.
  • P_input = P_output/η and I = P_input/(√3 V cos φ).
  • Overload relays protect against sustained overcurrent.
  • VFDs and soft starters reduce starting stress.
Practice

Worked example

A 15 kW motor with efficiency 0.92 and power factor 0.88 at 400 V draws P_input = 15 000 ÷ 0.92 = 16 304 W and I = 16 304 ÷ (√3 × 400 × 0.88) = 26.7 A.