Industrial Power Distribution

From the supply transformer to the distribution board: three-phase ratings, current per phase and the information a single-line diagram must provide.

In this lesson
  • Calculate the rated line current of a three-phase transformer from its kVA rating
  • Read the main quantities on a single-line diagram
  • Explain why distribution is three-phase rather than single-phase

Industrial installations take power at a distribution voltage and transform it to the level used by motors, drives and control equipment. A single-line diagram summarises the transformers, protective devices, busbars and feeders, and it is the reference document for any work on the installation.

S = √3 × V_line × I_line
Apparent power in a balanced three-phase system; S in volt-amperes, V in volts and I in amperes.
I_line = S ÷ (√3 × V_line)
Rated line current from apparent power and line voltage.
Worked example

Transformer rated current

Problem. A three-phase transformer is rated 100 kVA with a 400 V secondary. What is its rated secondary line current?

Solution. I = 100 000 ÷ (√3 × 400) = 100 000 ÷ 692.8 = 144.3 A.

Three-phase distribution

Three-phase distribution delivers the same total power with less conductor material and a steadier power flow than several single-phase circuits. It also provides a natural supply for three-phase motors, which are the dominant industrial load.

  • The kVA rating fixes the current for a given voltage.
  • The single-line diagram identifies sources, protections, feeders and loads.
  • Distribution voltage levels and earthing arrangements are site- and country-specific.
  • Balance single-phase loads across the phases where the design allows it.
Only authorised persons may open energised distribution equipment. The voltage, prospective fault current and earthing arrangement must be taken from the installation documentation and a site risk assessment, never guessed.
Key points.
  • S = √3 V_L I_L for a balanced three-phase system.
  • Rated current follows from kVA and line voltage.
  • The single-line diagram is the authority for the installation.
  • Three-phase distribution suits large motors and balanced loads.
Practice

Worked example

A 250 kVA transformer with a 400 V secondary has a rated line current of 250 000 ÷ (√3 × 400) = 360.8 A.