Industrial Safety and Lockout-Tagout

Arc and shock hazards, stored energy, the lockout-tagout sequence and the discipline of proving an installation dead.

In this lesson
  • Identify the main electrical hazards of industrial equipment
  • Apply a complete lockout-tagout sequence
  • Explain why stored energy must be released and verified

Industrial electrical work exposes people to shock, arc flash, arc blast and fire. An arc can release intense heat, light and pressure in a fraction of a second, and the resulting hazard is not limited to the electrical contact itself. The only reliable protection is to de-energise, isolate, lock, tag and prove dead before work begins.

Lockout-tagout sequence

Lockout-tagout is a controlled procedure, not a single action. It identifies every energy source, isolates it, applies a personal lock and tag, releases stored energy and verifies the absence of voltage. Only the person who applied a lock should remove it, under the site procedure.

  • Identify all sources, including control supplies, backfeeds and stored energy.
  • Notify affected people before isolation.
  • Isolate, lock and tag each source with a personal lock.
  • Release stored energy: capacitors, springs, elevated loads and pressurised systems.
  • Prove the tester on a known source, test the conductors, then re-prove the tester.
  • Verify the isolation at the point of work before touching anything.
E = ½ × C × V²
Energy stored in capacitance, which must be released and verified before work.
Worked example

Stored energy in a DC-bus capacitor

Problem. A 1000 µF capacitor is charged to 400 V. What energy does it store?

Solution. E = ½ × 1000 × 10⁻⁶ × 400² = 0.5 × 1000 × 10⁻⁶ × 160 000 = 80 J. Energy of this order is hazardous and must be treated with the site’s stored-energy procedure.

Arc hazard awareness

Arc flash risk depends on the available fault current, the protection settings, the working distance and the equipment condition. Arc-rated clothing and a formal risk assessment are used where the assessment shows an arc hazard; the required boundaries and PPE categories are defined by the site’s electrical safety programme and local regulation.

This lesson cannot replace a site safety programme. Arc boundaries, PPE levels and authorised-person requirements are jurisdiction- and installation-specific; follow the site procedure and the local standard.
Key points.
  • De-energise, isolate, lock, tag and prove dead.
  • Stored energy must be released and verified.
  • An arc flash is a heat, light and pressure hazard.
  • Arc boundaries and PPE are defined by assessment and local rules.
Practice

Worked example

Before working on a motor feeder, the isolator is opened, locked and tagged, the control supply is isolated, the drive’s DC-bus energy is allowed to discharge per the manufacturer’s instructions, and the feeder is tested dead at the point of work with a proved tester.