Lesson 4 of 4 35 min

Three-Phase Systems

Balanced three-phase supply, star and delta connections, line versus phase quantities and the three-phase power formula.

In this lesson
  • Describe the phase relationship of a balanced three-phase supply
  • Distinguish line and phase voltages and currents
  • Calculate active power in a balanced three-phase load

A balanced three-phase supply provides three sinusoidal voltages of equal magnitude, displaced by 120° in phase. This arrangement gives a constant total power transfer for a balanced load, which is why it dominates industrial power distribution and large motor drives.

Star and delta connections

In a star connection the three windings share a neutral point; in a delta connection they form a closed triangle. The relationship between line and phase quantities depends on the connection, so always identify which quantity a measurement refers to before applying a formula.

P = √3 × V_line × I_line × cos φ
Active power in a balanced three-phase load; V_line in volts, I_line in amperes and cos φ the power factor.
Worked example

Balanced three-phase power

Problem. A balanced load draws 20 A per line from a 400 V line-to-line supply at a power factor of 0.85. Calculate the active power.

Solution. P = √3 × 400 × 20 × 0.85 = 1.7321 × 400 × 20 × 0.85 = 11 778 W, approximately 11.8 kW.

Why balance matters

A balanced load draws equal currents with a 120° displacement, so the neutral current of a star-connected load is ideally zero. Unbalanced loads produce neutral current and unequal phase voltages, which is why phase balance is checked in industrial installations.

  • The three phase voltages are equal in magnitude and 120° apart.
  • Total instantaneous power of a balanced load is constant.
  • Line and phase quantities differ by the connection type.
  • Neutral current is ideally zero only for a balanced star load.
Voltage levels, conductor identification and protection requirements for three-phase installations are defined by local standards and the site’s single-line diagram. Never infer them from a general lesson.
Key points.
  • Three phases are 120° apart.
  • Balanced three-phase power is P = √3 V_L I_L cos φ.
  • Star and delta connections change the line/phase relationship.
  • Unbalanced loads create neutral current.
Practice

Worked example

A 400 V, 30 A balanced load at power factor 0.9 draws P = √3 × 400 × 30 × 0.9 = 18 706 W, about 18.7 kW.