Power & Energy Intermediate 10 min read Nov 2026

Power Factor

Power factor is the ratio of active power to apparent power. A low power factor means more current for the same useful work, so cables and sources must be larger.

Definition

Power factor is the ratio of active power to apparent power in an AC circuit, equal to the cosine of the phase angle between sinusoidal voltage and current. It indicates how much of the current is doing useful work.

Learning objectives

  • Define power factor and relate it to the phase angle
  • Calculate active, reactive and apparent power
  • Determine the reactive power needed for correction
  • Explain why low power factor increases current and losses
  • Measure power factor with a power analyser
Power Factor diagram Power relationship triangle P V I P = V × I
Power Factor — schematic illustration
Advertisement

Progressive explanation

Start with the plain-language idea, then move into the engineering detail. Each level stands on its own, so you can stop at the depth you need.

Beginner The core idea
In an AC circuit, some current may be used to build magnetic fields rather than do useful work. Power factor compares the useful power with the total power that appears to flow. A power factor of 1 means all the current is useful; 0.5 means only half of the apparent power is active.

Motors, transformers, ballasts and many electronic loads have a power factor below 1. The utility must supply the extra current even though the customer uses only the active power, so a low power factor increases losses and may be penalised.
Intermediate How it behaves in a circuit
For sinusoidal quantities, PF = P/S = cos φ, where S = Vrms × Irms is the apparent power in VA and P is the active power in W. The reactive power is Q = √(S² − P²) in var. A lagging power factor indicates an inductive load; a leading power factor indicates a capacitive load.

Capacitor correction reduces the reactive component: Qc = P × (tan φ1 − tan φ2), where φ1 is the initial angle and φ2 the target angle. Correction raises the power factor and reduces the supply current without changing the active power of the load.
Advanced Limits, assumptions, engineering detail
Distortion changes the simple picture: the true power factor is P/(Vrms × Irms) and includes harmonic content, while the displacement power factor is cos φ at the fundamental frequency. Capacitor banks can resonate with the supply inductance and amplify harmonics, so detuned reactors or active filters may be required. Over-correction produces a leading power factor and can raise the voltage. In three-phase systems, unbalance and harmonics make per-phase measurement necessary, and power factor is defined for the fundamental or for the total waveform depending on the standard and the instrument setting.

Formulas and variables

Power factor
PF = P / S = cos φ
PF Power factor · dimensionless P Active power · W S Apparent power · VA
P = 1840 W and S = 2300 VA give PF = 0.8.
Apparent power
S = Vrms × Irms
S Apparent power · VA Vrms RMS voltage · V Irms RMS current · A
230 V × 10 A = 2300 VA.
Capacitor correction
Qc = P × (tan φ1 − tan φ2)
Qc Reactive power to correct · var P Active power · W φ1 Initial phase angle · ° φ2 Target phase angle · °
1840 W from PF 0.8 to PF 0.95 needs about 775 var.

Units of measurement

QuantitySymbolUnit
Power factor PF dimensionless
Active power P watt (W)
Reactive power Q volt-ampere reactive (var)
Apparent power S volt-ampere (VA)

Worked examples

Worked example

Power triangle of a motor

Problem. A single-phase motor draws 10 A at 230 V with a power factor of 0.8 lagging. Find the apparent, active and reactive power.

Solution. S = 230 × 10 = 2300 VA. P = 2300 × 0.8 = 1840 W. Q = √(2300² − 1840²) = √(5 290 000 − 3 385 600) = √1 904 400.

S = 2300 VA, P = 1840 W and Q = 1380 var.
Worked example

Capacitor correction

Problem. The same 1840 W load has a power factor of 0.8. How much reactive power must be added to raise the power factor to 0.95?

Solution. φ1 = 36.87° so tan φ1 = 0.75. φ2 = 18.19° so tan φ2 = 0.329. Qc = 1840 × (0.75 − 0.329).

Qc ≈ 775 var.
Worked example

Current after correction

Problem. After correction to 0.95, what current does the 1840 W load draw from the 230 V supply?

Solution. S = P/PF = 1840/0.95 = 1937 VA. I = S/V = 1937/230.

I ≈ 8.42 A, down from 10 A, with the same active power.

Practical applications

  • Industrial electricity billing and demand charges
  • Motor and transformer loading
  • Generator and UPS sizing
  • Cable and switchgear sizing
  • Capacitor bank design
  • Energy-efficiency assessments

Automotive applications

Alternators, inverters and on-board chargers have their own power factor and distortion behaviour on the AC side. Electric-vehicle AC charging is specified with power-factor requirements so that the mains supply is not overloaded by reactive current.

Industrial applications

Factories with many induction motors often correct power factor with capacitor banks to avoid utility penalties and release transformer capacity. Where harmonics are present, detuned reactors or active filters are used instead of plain capacitors to avoid resonance.

Measurement procedure

  1. Use a power analyser that displays active, reactive and apparent power and the power factor together.
  2. Measure on the load side of the supply to distinguish load power factor from the corrected installation.
  3. Check whether the instrument reports displacement or true power factor when harmonics are present.
  4. Verify that voltage and current channels are connected with the correct polarity and phase.

Common mistakes

  • Confusing power factor with efficiency; a motor can have a good efficiency and a poor power factor.
  • Adding capacitors without checking for resonance with the supply and harmonics.
  • Assuming that correcting power factor reduces the energy bill; it mainly reduces current and kVA demand.
  • Ignoring distortion and trusting a displacement power-factor reading on a drive load.

Safety considerations

  • Capacitor banks retain charge after isolation; discharge them and verify before touching terminals.
  • Over-correction can raise the voltage and cause equipment problems; design correction for the actual load.
  • Arc-flash risk increases with large reactive banks and high fault levels; follow the switching procedure.

Frequently asked questions

Why do utilities charge for low power factor?
The utility must provide the extra current and capacity for reactive power even though the customer uses only active power. Commercial tariffs often include a reactive-power or kVA demand charge.
Can power factor exceed 1?
No. For sinusoidal quantities it is the cosine of an angle and lies between 0 and 1. A leading power factor is negative by convention but its magnitude is still at most 1.
What is the difference between displacement and true power factor?
Displacement power factor uses only the fundamental frequency. True power factor uses the total RMS voltage and current, so it also accounts for harmonic distortion.
Does power factor correction reduce kWh consumption?
It reduces current, losses in cables and transformers, and kVA demand. It does not reduce the active energy used by the load itself, apart from the reduction in distribution losses.